HYPERMIST SYSTEM
1) CHECK THAT THE SYSTEM IS LINED UP CORRECTLY.
2) CHECK PUMP IN AUTO MODE AND NO ALARMS ON THE FIRE CONTROL PANEL IN THE MSB ROOM.
3) TRYOUT AT LEAST ONE ZONE SPRINKLER RELEASE IN CONTROLLED MODE.
4) CHECK PUMP PRESSURE WHEN SYSTEM IS TESTED.
5) CHECK SPRINKLER HEADS FOR CLARITY (NO PAINT DEPOSITS ETC..)
CO2 SYSTEM
1) CHECK KEY IS IN PLACE.
2) CHECK INTEGRITY OF ALL THE CONNECTIONS
3) CHECK ALL CO2 HEADS FOR CLARITY
4) CHECK ROOM DOORS AND CABINET DOOR.
5) BLOW THROUGH WITH AIR.
QUICK CLOSING VALVE
1) VISUALLY INSPECT THE SYSTEM.
2) CHECK THE AIR PRESSURE IN THE BOTTLE
3) TRY OUT AT LEAST ONE SECTION OF QCVS. OR INDIVIDUAL VALVE FOR PROPER OPERATION
REMOTE TRIPS
1) FUNCTION TEST ONE SECTION AT A TIME..
EM'CY FIRE PUMP
1) ENSURE PUMP IS LINED UP AND READY FOR IMMEDIATE USE
2) TRIAL RUN FOR 10MINS AND RECORD THE PRESSURE GENERATED WITH TWO FIRE HOSES RIGGED.
3) CHECK FOR LEAKAGES
EM'CY GENERATOR
1) CHECK LO, FO, COOLING WATER LEVELS
2) CHECK E/GEN ON AUTO MODE.
3) TEST RUN THE ENGINE ON BATTERY MODE AND HYDRAULLIC STARTING MODE
4) CHECK OIL LEVEL IN HYD OIL TANK
5) TEST RUN ON LOAD FOR AT LEAST 30 MIN AND CHECK AVAILABILITY OF POWER AT SERVICES PROVIDED BY E/GEN.
SCBA COMPRESSOR
1) CHECK THE CONDITION OF CHARGING HOSES AND THE CONNECTIONS.
2) ENSURE ALL SCBA BOTTLES ARE FULLY CHARGED
3) CHECK OIL LEVEL IN THE SUMP
4) CHECK THE COMPRESSOR CUT OFF FUCNTION AT 300 BAR.
LIFE BOAT ENGINE
1) CHECK LO, FO AND COOLING WATER LEVEL.
2) TEST RUN THE ENGINE IN ALL RUNNING DIRECTIONS
3) CHECK SPRINKLER PUMP DRIVING MECHANISM
RESCUE BOAT ENGINE
1) CHECK LO, FO AND COOLING WATER LEVEL
2) TEST RUN THE ENGINE IN ALL RUNNING DIRECTIONS.
VENTILATION FLAPS
1) FUCNTION CHECK.
2) CHECK FOR ANY AIR LEAKS.
FIRE HYDRANTS AND HOSES
1) CHECK THAT ALL HOSES ARE IN PLACE AND GENERAL CONDITIONS ARE SATISFACTORY
2) CHECK FOR FREENESS OF NOZZLES, AND GREASE ACCORDINGLY.
3) PRESSURE TEST ALL HOSES ONCE IN THREE MONTHS
EM’CY BILGE SUCTION
1) OPERATE AND GREASE.
S.W. RECIRC. V/V
1) OPERATE FROM REMOTE AND LOCAL
STATIONS AND CONFIRM THE OPERATION.
STEAM SMOTHERING
SYSTEM
1) CARRY OUT VISUAL
INSPECTION OF THE SYSTEM AND CHECK INDIVIDUAL
UNIT V/V FOR FREENESS
INCINERATOR
1) TRY OUT TRIPS AND ALARMS.
SHIP SIDE V/V
1) OPERATE AND GREASE
FIRE AND GAS
DETECTION EQUIPMENTS
1) TEST ALL THE SENSORS
ONCE IN THREE MONTHS.
BILGE ALARMS
1) FUCNTION CHECK
BATTERIES AND
CHARGERS
2) CHECK THAT THE BATTERY IS FULLY
CHARGED.
3) EVERY QUARTER DISCHARGE ROUTINE
TO BE CARRIED OUT.
4) AFTER STARTING EM’CY GEN KEEP THE BATTERY IN
EQUALISING CHARGE
TILL BATTERY VOLTAGE
REACHED TO 27 V, THEN CHANGE OVER SWITCH TO
FLOATING CHARGE POSITION.
CRANES
1) FUCNTION CHECK THE
LIMIT SWITCHES
REF. CHAMBER ALARM
1) FUCNTION CHECK
O.W.S. 15 PPM
1) FUCNTION TEST OF
15-PPM ALARM AND CHANGING OVER OF O/B V/V
ELE. EM’CY TRIPS
1) CARRY OUT FUNCTION
TEST
2) CONFIRM ALL BREAKERS ASSOCIATED WITH THE GROUP HAVE TRIPPED.
EM’CY LIGHTING
1) FUCNTION CHECK
COMMUNICATION
EQUIPMENTS
1) FUCNTION CHECK
HAZ. AREA EQUIPMENTS
1) CHECK PHYSICAL
CONDITION OF THE EQUIPMENT
2) CHECK THE BONDING
M/E EM’CY MANOEUVRING
1) TRY OUT M/E FROM
LOCAL MANOEUVRING STATION.
EM’CY STEERING
1) TRY OUT STEERING FROM
LOCAL STATION.
MACHINERY TRIPS
1) TRY OUT TRIPS AND
ALARMS FOR MACHINERIES AS PER INDIVIDUAL SCHEDULES
BLACKOUT TEST
1) CARRY OUT BLACK OUT
TEST AND CHECK SEQUENTIAL START
EMERGENCY SHOWER
1) OPERATIONAL CHECK TO
BE CARRIED OUT.
2) OBSERVE THE COLOUR OF
WATER.